MBtek
APOLLO flow switch, black body, front view with LED indicator ladder

1 / 6

General-Purpose Flow Protection

APOLLO Pool Flow Switch

Adjustable non-mechanical thermal-dispersion flow protection for pool and general industrial water circuits.

Kit Configuration
Pool Flow Switch
$183
$14620% OFF

Shipping$80Free

Product added to cart.

View cart

Complete your system

  • Free shipping
  • Secure checkout

Product details

  • Six LEDs show flow against the setpoint
  • Normally open and normally closed contacts
  • 24 V DC
  • Setpoint adjusted on the unit

APOLLO Pool Flow Switch

Proves whether liquid is moving in the pipe. The setpoint is adjusted on the unit, and six LEDs show where the flow sits relative to that point. The relay provides normally open and normally closed contacts.

The LEDs are one red, one yellow, and four green. Red means the flow is below the setpoint: the normally closed contact is closed and the normally open contact is open. Yellow means the flow is at or above the setpoint: the normally closed contact opens and the normally open contact closes. Above the setpoint, one to four green LEDs show how far the flow is above it, in steps of about 20% of the full-pipe flow.

Power is 24 V DC on pins 1 and 3. The five wires are 1 brown, 2 white, 3 blue, 4 black, and 5 grey. Normally closed is pins 2 and 5. Normally open is pins 4 and 5.

The setpoint is an internal potentiometer under a sealing screw. Turn it clockwise to raise the setpoint. During setup, run normal flow for 3–5 minutes before adjusting, then wait 1–3 minutes for the switch to store the setting.

Key Benefits

  • Six LEDs show flow below, at, or above the setpoint
  • Normally open and normally closed relay contacts
  • 24 V DC
  • Setpoint adjusted on the unit
Indicators
6 LEDs: 1 red, 1 yellow, 4 green
Below setpoint
Red on. N.C. closed (pins 2 and 5). N.O. open (pins 4 and 5)
At or above setpoint
Yellow on. N.C. open. N.O. closed
Above setpoint
1 to 4 green LEDs, in steps of about 20% of full-pipe flow
Power
24 V DC, pins 1 and 3
Wires
1 brown, 2 white, 3 blue, 4 black, 5 grey
Adjustment
Potentiometer under the sealing screw. Clockwise raises the setpoint
Setup
3–5 minutes at normal flow before adjusting, then 1–3 minutes to store the setting

MBTEK Google Reviews

Verified Google reviews from MBTEK customers across our heating and hydronic product lines.

Loading reviews…

Installation help and contact

Need an installer?We made it easy for you.

Listed installers are independent contractors, not MBTEK employees. They're skilled professionals familiar with our products and capable of efficient installation.

Any questions?Reach out to us.

Our team can help with product questions, sizing guidance, and next steps.